Parameters
Supply voltage |
230 VAC ±10% |
Switched voltage |
3x400 VAC |
Internal power consumption |
up to 7 VA |
Power loss in a current circuit |
up to 5 W |
Residual current |
0.01 mA at 25°C |
Required external protection |
3 phases circuit-breaker up to 20 A |
Required external protection |
circuit-breaker 1 phase up to 2 A |
Internal protection |
10 A quick acting fuse |
Mechanical power of the controlled motor |
up to 7.5 kW ( 9 kW ) |
Control voltage |
24 VDC any polarisation |
Control input current |
12 mA DC |
Output voltage to the limit switches and to the motor thermo |
230 VAC |
Input current from limit switches and thermostat |
12 mA AC |
Working temperature |
0÷50°C |
Limit switches multiplication |
2 pairs of individual contacts |
Load capacity of switching contacts |
230 VAC/DC, 1 A |
Braking time adjusting |
0÷90 ms |
Description
Servoster-05 is an all-purpose electronic servodriver dedicated to control actuators working in modulating mode, both executing regulatory and on-off tasks. It performs contactless remote control of electric drives with three-phase electric motors up to 7.5kW. It supports main logic and linking features required for regulatory and controlling servomotor:
➡ contactless switching and reversing service duty of servomotor’s engine during heavy-duty action,
➡ remote motor’s slow down with energy recovery,
➡ three-points control duty directly from PLC driver, control panel or system,
➡ automatic servomotor stoppage in ultimate positions,
➡ automatic servomotor stoppage in absence of electric standby,
➡ co-operation with limit and torque switches and motor’s thermostat,
➡ duplication of limit switches,
➡ duplication of regulatory state and working mode,
➡ control signals’ hold up until drive reaches extreme position,
➡ hold up drive’s lock at terminal stop until reverse control signal appears,
➡ interaction with control panel or local control box,
➡ servicing of emergency stop button and additional block systems,
➡ LED signalling of servomotor’s field state and electric standby,
➡ internal protection against short circuits and phase’s fading.
|
|